- Go to the main menu (double press ESC).
- Go to settings (hold down the OK button for about three seconds).
- Use the arrows to locate PRIORITY in the settings and press OK.
- Use the arrow keys to locate Grid First mode and press OK.
- Then Grid First: NO will appear on the display - press OK again and use the arrows to select OK (note: if this mode cannot be started, it is because Export Limitation is not enabled - set here).
- Next, use the arrows to set the individual items:
- Time – select the time period in which the inverter should operate in Grid First mode
- Stop SOC – select the battery SOC value at which the inverter should stop drawing power from the batteries. After selecting the desired value, confirm the selection with OK
- Power Rate – select the power to be supplied from the inverter to the grid. This percentage power is taken with respect to the rated power of the inverter. After selecting the value, confirm the selection with OK.
- After setting all parameters in the last SAVE box, select OK using the OK button (this will confirm the settings).
- If the mode cannot be confirmed, there is probably a time conflict with Battery First mode and this time conflict needs to be reconfigured so that the usage times of the two modes do not cross each other.