Asymmetry setting
The asymmetry setting is done via the parameter LoadFirstControl:
- Go to the main menu (press ESC twice)
- Go to settings (hold OK for about three seconds)
- In the settings, use the arrows to locate ExportLimit and press OK
- When LoadFirstControlt: SiEn/ThEn is displayed, set SiEn (Press OK and use the arrow keys to select SiEn, then press OK again)
- Automatically switches on the inverter check (Checking 300 s)
Overflow settings
Enable ExportLimit (overflow limit)
- Go to the main menu (press ESC twice)
- Go to settings (hold OK for about three seconds)
- In the settings, use the arrows to locate ExportLimit and press OK
- After displaying ExportLimit: ON/OFF set to ON (Press OK and use the arrow keys to select ON, then press OK again)
- Automatically switches on the inverter check (Checking 300 s)
Enabling SingleExport (limiting overflows after one phase)
- Go to the main menu (press ESC twice)
- Go to settings (hold OK for about three seconds)
- In the settings, use the arrows to locate ExportLimit and press OK
- In the following menu, search for SingleExport: ON/OFF, set this value to ON similar to the ExportLimit setting
- Automatically switches on the inverter check (Checking 300 s)
PowerRate settings (overflow rate)
- Set the value of allowed overflows (Exportlimit 0%, Limit Power Rate = prohibited overflows)
- Go to the main menu (double press ESC)
- Go to settings (hold OK for about three seconds)
- In the settings, use the arrows to locate ExportLimit and press OK
- In the following menu, find PowerRate: XX.X%, set this value to ON similarly to the ExportLimit setting using the OK button and arrows.