- In OSS, after selecting the "Settings" icon, set the parameters as shown below. Set the parameters one at a time, i.e. after each parameter change, confirm its setting with the "Yes" button. This setting is valid for the case when overflows are disabled. Pay attention to the setting of the "Phase level" parameter, which must be set to "Enable".
- If you want to enable unlimited overflows, set the numeric value of the "Set Exportlimit" parameter to "100".
-
If you want to enable partial overflows, there is no need to have specific firmware installed on the inverter. In the "Set Exportlimit" parameter setting, you need to set a numerical value according to the allowed overflows. The value is related to the nominal power of the inverter (example: if you want to set the overflow size of 4 kW for the MOD 10KTL3-XH(BP) inverter, set the numerical value of the "Set Exportlimit" parameter to 40).
*** Translated with www.DeepL.com/Translator (free version) ***
Each time you set the inverter parameters, also select "Electric Meter" in the "Dynamometer" parameter. This setting ensures communication between the inverter and the smartmeter.
Note: When setting parameters, always set one parameter and confirm with the "Yes" button. Then set another parameter and confirm again with the "Yes" button.