- Allowable overflows without limitations - overflows are limited by the maximum inverter output.
- Forbidden overflows - values can be in the range of 0 - 150 W for long periods of time (both during delivery from the battery and during PV generation damping), which meets the requirements for ¼ hourly maximums to avoid penalties.
- Partially permitted overflows – Firmware 050510 and higher, which supports the dynamic export limit function, is required for proper operation. The inverter then allows overflows within the configured power and maintains asymmetric operation.
Note: Testing of the control capability is carried out both in the SOLSOL test laboratory and in real household operation on multiple properties (OM). The measurement is also validated with the distribution companies' billing metering. When the inverter is properly wired and set up, the quarter-hourly maximum measured by the distribution companies was always below 300 W.
It should be noted that in real operation, unpredictable external influences, such as those related to the behaviour of connected appliances, may affect the control capability. In this case, SOLSOL is not responsible for any financial penalties that may arise in case of exceeding the reserved capacity.